Sample Thermography Report
Equipment Surveyed: MCC-1 Motor Controller

Location: 1st Floor Electrical Room
Problem: Poor crimp at Bf load side conductor to lug connection
Date: Today
Time: 9:55:33 AM
Surveyor: Patrick Howell
Max 70.7°C, Distance 1 m
Reference Temp 39.2° C, Ambient Air Temp 26° C
Degrees over ambient
31.5°C, Humidity 50%

Recommendation: Replace conductor. Terminal connection is satisfactory, but the conductor needs to be replaced due to heat damage caused by a poor crimp at the lug